Idea Statica
  • Steel
  • Concrete
  • BIM & Workflows
  • Support & Learning
  • Pricing
  • Company
  • Steel overview
  • Connection design
  • Member design
  • Parametric design
  • Steel case studies
  • Concrete overview
  • Walls and D-regions
  • Anchoring design
  • Concrete case studies
  • BIM Overview
  • Supported integrations
  • Checkbot
  • Viewer
  • APIs
  • Support Center
  • E-learning & certification
  • Blog
  • Downloads & Licensing
  • Plans
  • Free community tool
  • Enterprise customers
  • Students & educators
  • How much will you save?
  • About us
  • Contact
  • Research & development
  • Authorized resellers
  • Meet our customers
  • Career
  • Steel
    Steel overviewConnection designMember designParametric designSteel case studies
  • Concrete
    Concrete overviewWalls and D-regionsAnchoring designConcrete case studies
  • BIM & Workflows
    BIM OverviewSupported integrationsCheckbotViewerAPIs
  • Support & Learning
    Support CenterE-learning & certificationBlogDownloads & Licensing
  • Pricing
    PlansFree community toolEnterprise customersStudents & educatorsHow much will you save?
  • Company
    About usContactResearch & developmentAuthorized resellersMeet our customersCareer
14-Day Trial
14-Day Trial

Subscribe to our newsletter

Company

  • About us
  • Partners
  • Careers
  • Patent

Resources

  • Customer projects
  • Case studies
  • Connection Library
  • Verification books

Legal

  • EULA
  • Global privacy policy
  • California Privacy
  • TOS Viewer
  • Licensing

Help

  • Contact
  • Quote request
  • Resellers
  • Downloads
FacebookInstagramLinkedInYouTube

© IDEA StatiCa 2009-2026

Trusted and used worldwide by engineers, fabricators & consultants.

Support CenterVerification examplesBolted splice connection (AISC)
Bolted splice connection (AISC)
SteelConnection designVerificationsAISC (USA)CBFEM

Bolted splice connection (AISC)

This article is also available in
ENCZDEESFRITPTNLHUROKRPLTHTRVIZH

Subcode: LRFD

Type of connection: Bolted splice connection

Unit system: Metric

Designed acc. to: AISC 360-16

Investigated: Bolts in shear and bearing

Plate material: A709, Gr. 50

Bolts: 5/8'' A307

Geometry

Applied load

Bolted splice connection is loaded by tension for the bolts in shear to be utilized at 100 %.

Procedure

Concentrically loaded splice bolted connection is designed so that bolts fail in shear (AISC 360-16 – J3.6). Bolt strength in bearing (AISC 360-16 – J3.10) and strength of plates in tension (AISC 360-16 – J4.1) are also checked. The bolt threads are intercepted by the shear plane.

Manual calculation

Bolt strength

The resistance of one shear plane of one bolt in shear is 27.6 kN. Each bolt has two shear planes and there are 9 bolts at each half of the splice. The resistance is therefore 2 ∙ 9 ∙ 27.6 = 496.7 kN.

The bearing strength and tearout strength resist the force acting on both shear planes, i.e. 2 ∙ 27.6 = 55.2 kN. The smallest strength is the tearout strength of bolts near the edge of connected plates with the thickness of 10 mm, 121 kN. Other bolts have bearing strength of 128.1 kN and the decisive is the plate with the thickness of 10 mm. The sum of thicknesses of splices resisting in bearing is 12 mm.

Strength of plates in tension

ϕRn=ϕFyAg=0.9⋅344.7⋅2000=620.46 kN\phi R_n = \phi F_y A_g = 0.9 \cdot 344.7 \cdot 2000 = 620.46 \, \textrm{kN}ϕRn​=ϕFy​Ag​=0.9⋅344.7⋅2000=620.46kN

ϕRn=ϕFuAe=0.75⋅448.2⋅1476=496.16 kN\phi R_n = \phi F_u A_e = 0.75 \cdot 448.2 \cdot 1476 = 496.16\,\textrm{kN}ϕRn​=ϕFu​Ae​=0.75⋅448.2⋅1476=496.16kN

Check in IDEA StatiCa Connection

There are some tensile forces in bolts due to plate deformation. Bolts are utilized at 99.9 % and plates are yielding. From the plastic strain at the connected plate, it can be seen that the reserve is not very high.

Comparison

The tensile forces in bolts are neglected in manual calculation but they do not affect the shear strength of bolts by much. The load resistance in IDEA StatiCa Connection is 494 kN while in manual calculation, it is 496 kN. In IDEA StatiCa Connection, bolts are decisive and the plates are yielding. In manual calculation, the bolts and plate tensile rupture have the same load resistance. The difference between results provided by software and manual calculation is only 0.4 %.

Open in ViewerDownload